Description
Wall Thermostat
It is a non-programmable wall thermostat specifically designed for use with the AZ9V series (Phase 2) Vertical Terminal Air Conditioners (VTACs). This thermostat offers straightforward temperature control and is tailored to integrate seamlessly with compatible GE VTAC units.
Specifications
Dimension
Electrical Specifications
Voltage:
24 VAC (operating range: 18–30 VAC)
Current:
1 amp maximum per terminal; 4 amp maximum total load
Temperature Settings
Operating range:
40°F–99°F (4°C–37°C)
Setpoint range:
60°F–85°F (15°C–29°C)
System Configurations
Factory Setting:
3-stage heat,2-stage cool,2-speed fan
Alternate Settings:
2 & 1 Stage Heat
Wiring Specifications
Terminals:
R, C, B, Y1, W, Y2, GL, GH
Maximum wiring length:
66 ft (20 meters) for AWG18 wire
Features
Compatibility
- Engineered for the AZ9V series (Phase 2) VTAC units, ensuring optimal performance and integration.
User-Friendly Interface
- Equipped with easy-to-use up and down buttons and a backlit LED display for clear visibility and simple operation.
California residents see
Prop 65 WARNINGS